Part Number |
3RK1301-1BB00-1AA2 |
Manufacturer |
Siemens |
Product Brand Name |
Sirius |
Product Designation |
Motor Starter ET 200S |
Design of the Product |
Reversing Starter |
Product Function |
Bus-communication, Reverse Starting, Short Circuit Protection |
Design of the Switching Contact |
Electromechanical |
Product Component |
Outlet for Engine Brake |
Trip Class |
CLASS 10 |
Type of Assignment |
2 |
Product Extension |
Braking Module for Brake Control |
Supply Voltage |
24 V DC |
Control Supply Voltage |
20.4 ... 28.8 V DC |
Operating Voltage |
400 ... 500 V |
Adjustable Response Current |
1.4 ... 2 A |
Service Power |
0.75 kW at 400 V AC-3 |
Breaking Capacity Limit |
50 kA at 400 V |
Number of Poles |
3 |
Type of Motor Protection |
Bimetal |
Mechanical Operating Cycles |
100,000 |
Mounting Type |
Pluggable on Terminal Module |
Dimensions (H x W x D) |
265 mm x 90 mm x 120 mm |
Mounting Position |
Vertical, Horizontal |
Installation Altitude |
Up to 2,000 m |
Ambient Temperature (Operation) |
0 ... 60 °C |
Ambient Temperature (Storage) |
-40 ... +70 °C |
Relative Humidity (Operation) |
5 ... 95 % |
Communication Protocols Supported |
PROFIBUS DP, PROFINET |
Electrical Connection |
Screw-type Terminals, Plug, Energy Bus, Backplane Bus |
EMC Standards |
CISPR11, IEC 60947-1, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-3 |
Certificates/Approvals |
CE, UL, CSA, CCC |
Protection Class |
IP20 |
Degree of Pollution |
3 at 400 V, 2 at 500 V according to IEC60664 (IEC61131) |
Resistance Against Vibration |
2g |
Resistance Against Shock |
5g / 11 ms |
Degree of Protection Against Electric Shock |
Finger-safe |
Product Function (Bus Communication) |
Yes |
Product Function (Direct Start) |
No |
Product Function (Reverse Starting) |
Yes |
Product Function (On-site Operation) |
Yes |
Product Function (Short Circuit Protection) |
Yes |
Product Function (Supports PROFIenergy Measured Values) |
No |
Product Function (Supports PROFIenergy Shutdown) |
No |
Address Range Memory (Inputs) |
1 byte |
Address Range Memory (Outputs) |
1 byte |
Power Loss (Switching State OFF) |
0.374 W |
Power Loss (Switching State ON) |
4.118 W |
Impulse Voltage Resistance |
6 kV |
Insulation Voltage |
500 V |
Active Power Loss |
10 W |
Maximum Permissible Voltage for Safe Disconnection |
400 V between main circuit and auxiliary circuit |
Mechanical Service Life |
100,000 switching cycles |
Type of Assignment |
2 |
Reference Code (DIN EN 61346-2) |
Q |
Reference Code (DIN 40719) |
A |
Product Function (Direct Start) |
No |
Product Component (Motor Brake Output) |
Yes |
Product Feature (Brake Control with 230 V AC) |
No |
Product Feature (Brake Control with 24 V DC) |
No |
Product Feature (Brake Control with 180 V DC) |
No |
Product Feature (Brake Control with 500 V DC) |
No |
Product Extension (Braking Module for Brake Control) |
Yes |
Product Function (Short Circuit Protection) |
Yes |
Design of Short-circuit Protection |
Circuit-breakers |
Maximum Short-circuit Current Breaking Capacity |
50 kA at 400 V |
EMC Emitted Interference |
CISPR11, ambience A (industrial sector) |
EMI Immunity |
IEC 60947-1, degree of severity 3, ambience A (industrial sector) |
Conducted Interference (Burst) |
IEC 61000-4-4, 2 kV on voltage supply, inputs and outputs |
Conducted Interference (Surge) |
IEC 61000-4-5, 2 kV (U > 24 V DC) |
Field-bound Parasitic Coupling |
IEC 61000-4-3, 80 MHz ... 1 GHz 10 V/m, 1.4 GHz ...2 Hz 3 V/m, 2 GHz ... 2.7 GHz 1 V/m |
Safety Related Data |
B10 value: 1,000,000, Proportion of dangerous failures: 50% (low demand rate), 75% (high demand rate) |
Failure Rate [FIT] |
- |