Part Number |
RM35UB3N30 |
Manufacturer |
Schneider |
Product Type |
Control Relay |
Application |
For 3-phase supply monitoring |
Relay Name |
RM35UB3 |
Monitored Parameters |
Absence of neutral, overvoltage and undervoltage between phases and neutral |
Time Delay Type |
Adjustable 0.3 to 30 seconds, ±10% on threshold crossing |
Switching Capacity |
1250 VA |
Minimum Switching Current |
10 mA at 5 V DC |
Maximum Switching Current |
5 A AC/DC |
Power Consumption |
≤ 3.9 VA AC |
Measurement Range |
114 to 329 V AC, 50/60 Hz |
Utilisation Category |
AC-12, AC-13, AC-14, AC-15, DC-12, DC-13, DC-14 according to IEC 60947-5-1 |
Contact Type and Composition |
2 C/O (Changeover) contacts |
Reset Time |
1500 ms for time delay |
Maximum Switching Voltage |
250 V AC/DC |
Rated Supply Voltage |
120 to 277 V AC, 50/60 Hz ±10% |
Supply Voltage Limits |
114 to 329 V AC |
Voltage Detection Threshold |
114 V |
Control Circuit Frequency |
50 to 60 Hz ±15% |
Output Contacts |
1 C/O + 1 C/O, 1 per threshold |
Nominal Output Current |
5 A |
Measuring Cycle |
≤ 150 ms measurement cycle as true RMS value |
Hysteresis |
2% |
Run Up Delay at Power Up |
≤ 650 ms |
Measurement Accuracy |
±10% of the full scale value |
Repeat Accuracy |
±0.5% for input and measurement circuit, ±1% for time delay |
Measurement Error |
<1% over the whole range with voltage variation |
Response Time |
<200 ms in the event of a fault |
Quality Labels |
CE |
Overvoltage Category |
III according to IEC 60664-1 |
Insulation Resistance |
> 500 MOhm at 500 V DC according to IEC 60255-5 and IEC 60664-1 |
Rated Insulation Voltage |
400 V according to IEC 60664-1 |
Operating Position |
Any position without derating |
Connections - Terminals |
Screw terminals for various wire types and sizes |
Tightening Torque |
0.6 to 1 N.m according to IEC 60947-1 |
Housing Material |
Self-extinguishing plastic |
Local Signalling |
LED indicators for power ON and relay ON |
Mounting Support |
35 mm symmetrical DIN rail according to IEC 60715 |
Electrical Durability |
10000 cycles |
Mechanical Durability |
30000000 cycles |
Operating Rate |
≤ 360 operations/hour under full load |
Safety Reliability Data |
MTTFd = 502.2 years, B10d = 470000 |
Width |
35 mm |
Net Weight |
0.08 kg |
Functionality |
Overvoltage and undervoltage detection |
Compatibility Code |
RM3 |
Electromagnetic Compatibility |
Emission standards for industrial, residential, commercial, and light-industrial environments |
Standards |
EN/IEC 60255-1 |
Product Certifications |
UL, C-Tick, GL, CSA, GOST |
Directives |
89/336/EEC - electromagnetic compatibility, 73/23/EEC - low voltage directive |
Ambient Air Temperature |
For storage: -40 to 70 °C, for operation: -20 to 50 °C |
Relative Humidity |
95% at 55 °C according to IEC 60068-2-30 |
Vibration Resistance |
0.35 mm (f = 5 to 57.6 Hz), 1 gn (f = 57.6 to 150 Hz) according to IEC standards |
Shock Resistance |
5 gn according to IEC 60068-2-27 |
IP Degree of Protection |
IP20 (terminals), IP30 (casing) according to IEC 60529 |
Pollution Degree |
3 according to IEC 60664-1 |
Dielectric Test Voltage |
2 kV AC 50 Hz, 1 min |
Non-dissipating Shock Wave |
4 kV |