Part Number |
LC1D115BD |
Manufacturer |
Schneider Electric |
Product Type |
Contactor |
Utilisation Category |
AC-1, AC-3, AC-4 |
Poles Description |
3P (3 NO) |
Rated Operational Voltage |
Power circuit: ≤ 1000 V AC 25...400 Hz, Power circuit: ≤ 300 V DC |
Rated Operational Current |
200 A (at <60°C) at ≤ 440 V AC AC-1 for power circuit, 115 A (at <60°C) at ≤ 440 V AC AC-3 for power circuit |
Motor Power kW (AC-3) |
30 kW at 220...230 V AC 50/60 Hz, 55 kW at 380...400 V AC 50/60 Hz, 59 kW at 415...440 V AC 50/60 Hz, 75 kW at 500 V AC 50/60 Hz, 80 kW at 660...690 V AC 50/60 Hz, 65 kW at 1000 V AC 50/60 Hz |
Motor Power HP (UL/CSA) |
30 hp at 200/208 V AC 50/60 Hz for 3 phases motors, 40 hp at 230/240 V AC 50/60 Hz for 3 phases motors, 75 hp at 460/480 V AC 50/60 Hz for 3 phases motors, 100 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
Control Circuit Type |
DC standard |
Control Circuit Voltage |
24 V DC |
Auxiliary Contact Composition |
1 NO + 1 NC |
Rated Impulse Withstand Voltage |
8 kV conforming to IEC 60947 |
Overvoltage Category |
III |
Conventional Free Air Thermal Current |
200 A (at 60°C) for power circuit |
Rated Making Capacity |
1260 A at 440 V for power circuit conforming to IEC 60947 |
Rated Breaking Capacity |
1100 A at 440 V for power circuit conforming to IEC 60947 |
Rated Short-time Withstand Current |
250 A 40°C - 10 min, 550 A 40°C - 1 min, 950 A 40°C - 10 s, 1100 A 40°C - 1 s for power circuit |
Associated Fuse Rating |
250 A gG at ≤ 690 V coordination type 1, 200 A gG at ≤ 690 V coordination type 2 for power circuit |
Average Impedance |
0.6 mOhm - Ith 200 A 50 Hz for power circuit |
Rated Insulation Voltage |
Power circuit: 600 V CSA certified, Power circuit: 600 V UL certified, Power circuit: 1000 V conforming to IEC 60947-4-1, Signalling circuit: 690 V conforming to IEC 60947-1, Signalling circuit: 600 V CSA certified, Signalling circuit: 600 V UL certified |
Electrical Durability |
0.8 Mcycles 200 A AC-1 at Ue ≤ 440 V, 0.95 Mcycles 115 A AC-3 at Ue ≤ 440 V |
Power Dissipation per Pole |
24 W AC-1, 7.9 W AC-3 |
Standards |
CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508 |
Product Certifications |
CCC, UL, BV, CSA, GL, GOST, DNV, LR, RINA |
Connections - Terminals |
Control circuit: screw clamp terminals, Power circuit: connector for cables |
Tightening Torque |
Control circuit: 1.2 N.m, Power circuit: 12 N.m |
Operating Time |
20...35 ms closing, 40...75 ms opening |
Mechanical Durability |
8 Mcycles |
Maximum Operating Rate |
1200 cyc/h at 60°C |
Coil Technology |
With integral suppression device |
Control Circuit Voltage Limits |
Operational: 0.75...1.2 Uc DC at 55°C, Drop-out: 0.15...0.4 Uc DC at 55°C |
Time Constant |
25 ms |
Inrush Power |
270…365 W at 20°C |
Hold-in Power Consumption |
2.4…5.1 W at 20°C |
Signalling Circuit Frequency |
25...400 Hz |
Minimum Switching Current |
5 mA for signalling circuit |
Minimum Switching Voltage |
17 V for signalling circuit |
Non-overlap Time |
1.5 ms on de-energisation and energisation between NC and NO contact |
Insulation Resistance |
> 10 MOhm for signalling circuit |
IP Degree of Protection |
IP20 front face conforming to IEC 60529 |
Protective Treatment |
TH conforming to IEC 60068-2-30 |
Pollution Degree |
3 |
Ambient Air Temperature for Operation |
-40…60°C, 60…70°C with derating |
Ambient Air Temperature for Storage |
-60…80°C |
Operating Altitude |
0...3000 m without derating |
Fire Resistance |
850°C conforming to IEC 60695-2-1 |
Flame Retardance |
V1 conforming to UL 94 |
Mechanical Robustness |
Vibrations: contactor open 2 Gn, 5...300 Hz, contactor closed 4 Gn, 5...300 Hz, Shocks: contactor closed 15 Gn for 11 ms, contactor open 6 Gn for 11 ms |
Dimensions (Height x Width x Depth) |
158 mm x 120 mm x 136 mm |
Net Weight |
2.5 kg |